Our duct size calculator finds the right duct diameter or width for the airflow you need. Enter the CFM, choose the duct section and material, and it sizes the duct using the velocity limits in ACCA Manual D.
Ducts that are too small make your system loud and starve rooms of air. Ducts that are too big cost more and take up space you may not have. This tool helps you land in between, and it can also check whether a duct you already have is moving air too fast.
Quick answer: To size a duct, divide the airflow in CFM by the target air velocity in feet per minute to get the area in square feet. For a round duct, diameter in inches equals 12 times the square root of (4 × area ÷ 3.1416). For example, 1,000 CFM at 700 FPM needs a 16.2-inch duct, so you’d use 18 inches.
Duct Size Calculator
Find the right round or rectangular duct size from airflow and air velocity.
Formula: Area (sq ft) = CFM / Velocity (FPM), Round diameter (in) = 12 x square root of (4 x Area / 3.1416), velocity limits from ACCA Manual D, Table 3-1
Results are estimates using the velocity method. Long runs and many fittings also need a friction-rate check.
How to Use the Duct Size Calculator
The calculator uses the velocity method. It picks a target air speed for the type of duct you're sizing, then finds the smallest standard duct that keeps air at or below that speed.
Inputs
- Airflow (required): the CFM this duct must carry. For a branch, that's the airflow for one room. For a trunk, it's the total for every room it feeds.
- Duct section (required): supply trunk, supply branch, return trunk or return branch.
- Duct material (required): rigid metal or flexible duct.
- Duct shape (required): round or rectangular. For rectangular ducts, you'll also enter the height.
- Existing duct size (optional): a diameter or width you already have, so the calculator can check its air speed.
Outputs
- The recommended standard round size, or the width for a rectangular duct at your chosen height
- The target and maximum velocity for that duct section
- The exact required area and diameter or width
- The air velocity at the recommended size, and in your existing duct if you entered one
- For rectangular ducts, the equivalent round diameter
- A status badge: Within range, Borderline or High
Who should use it and when
It's useful for homeowners finishing a basement or adding a room, for DIYers checking a contractor's plan, and for technicians and students working through duct problems. Use it when you're adding a run, replacing a section or tracking down a noisy register.
The Duct Sizing Formula
Area (sq ft) = Airflow (CFM) ÷ Velocity (FPM)
Round diameter (in) = 12 × √(4 × Area ÷ 3.1416)
Rectangular width (in) = Area × 144 ÷ Height (in)
Actual velocity (FPM) = CFM ÷ Area of the duct you choose
| Variable | Meaning | Unit |
|---|---|---|
| CFM | Airflow the duct must carry | Cubic feet per minute |
| Velocity | Speed of air inside the duct | Feet per minute (FPM) |
| Area | Inside cross-section of the duct | Square feet (× 144 for square inches) |
| Diameter, width, height | Duct dimensions | Inches |
Target velocities from Manual D
The calculator sizes each duct to the recommended velocity and flags anything above the maximum. These values come from ACCA Manual D, Table 3-1.
| Duct section | Recommended, rigid | Maximum, rigid | Recommended, flex | Maximum, flex |
|---|---|---|---|---|
| Supply trunk | 700 FPM | 900 FPM | 600 FPM | 700 FPM |
| Supply branch | 600 FPM | 900 FPM | 600 FPM | 700 FPM |
| Return trunk | 600 FPM | 700 FPM | 600 FPM | 700 FPM |
| Return branch | 400 FPM | 700 FPM | 400 FPM | 700 FPM |
Step-by-step calculation
- Find the recommended velocity for your duct section and material in the table.
- Divide the CFM by that velocity to get the required area in square feet.
- For round duct, convert the area to a diameter. For rectangular duct, divide the area in square inches by the height.
- Round up to the next standard size. Round ducts commonly come in 1-inch steps up to 10 inches and 2-inch steps above that. The calculator rounds rectangular widths up to the next even inch.
- Check the actual velocity at the size you picked.
Worked example
You need a rigid round supply trunk that carries 1,000 CFM. You also want to check an existing 16-inch trunk.
- Recommended velocity: 700 FPM (maximum 900 FPM)
- Required area: 1,000 ÷ 700 = 1.429 sq ft, or 205.7 square inches
- Exact diameter: 12 × √(4 × 1.429 ÷ 3.1416) = 16.2 inches
- Next standard size: 18 inches, where air moves at about 566 FPM
- Existing 16-inch duct: area 1.396 sq ft, so air moves at about 716 FPM
An 18-inch trunk is within range. The existing 16-inch trunk runs at 716 FPM, which is above the 700 FPM target but below the 900 FPM maximum. That's borderline. It'll work, but it may be a bit noisier and add some resistance.
If you'd rather use a rectangular trunk 8 inches tall, the required width is 205.7 ÷ 8 = 25.7 inches. Rounded up, that's a 26 × 8-inch duct with air at about 692 FPM.
What Your Result Means
The status badge and gauge compare the air velocity with the Manual D limits for your duct section and material.
| Velocity | Status | What it means |
|---|---|---|
| At or below the recommended value | Within range (green) | Quiet, efficient airflow with reasonable pressure loss |
| Above recommended, up to the maximum | Borderline (amber) | Works, but expect more noise and resistance. One size larger usually fixes it. |
| Above the maximum | High (red) | Likely whistling, drafts and reduced airflow. Use a larger duct or split the airflow. |
Low velocity isn't a problem in itself. It just means the duct is larger than it needs to be, which costs more and takes more space.
Common Mistakes
- Using system CFM for a branch. A branch only carries the airflow for its own room. Use the room's CFM, not the whole system's.
- Sizing flex duct like metal. Flexible duct has lower velocity limits and more friction, especially when it's stretched loosely or kinked.
- Ignoring long runs and fittings. Velocity is only half the picture. Long runs, elbows and boots add friction, which Manual D handles with a friction-rate method.
- Making rectangular ducts too flat. A wide, short duct has more friction than a round duct with the same area. The calculator shows the equivalent round diameter so you can compare.
- Forgetting leaks. ENERGY STAR estimates that about 20 to 30 percent of the air moving through a typical duct system is lost to leaks, holes and poor connections. A perfectly sized duct still needs sealed joints.
Practical Tips
- Get the airflow right first. The Department of Energy says heat pumps need about 400 to 500 CFM per ton. Our CFM Calculator can help you estimate room airflow.
- Size the trunk for the rooms it feeds. Add up the branch CFMs downstream of each section. Trunks can often step down in size after branches take off.
- Prefer round where it fits. Round duct has less friction for the same airflow and is easier to seal.
- Check grilles and registers too. Manual D lists face velocities of about 500 FPM for return grilles and 300 FPM for filter grilles. Our Return Air Grille Size Calculator covers that step.
- Seal with mastic or foil tape. Cloth duct tape doesn't last on ductwork.
- Get a Manual D design for new systems. For a full duct layout, a contractor should design it with ACCA Manual D.
Related calculators: find the system size first with the Heat Pump Size Calculator (most systems move about 350 to 400 CFM per ton), or browse all HVAC calculators.
Summary Table
| Item | Details |
|---|---|
| Inputs | Airflow (CFM), duct section, material, shape, height for rectangular ducts, existing size (optional) |
| Formula | Area = CFM ÷ Velocity; Diameter = 12 × √(4 × Area ÷ 3.1416); Width = Area × 144 ÷ Height |
| Outputs | Standard duct size, exact size, velocity, equivalent round diameter, status |
| Best use cases | Adding or replacing runs, checking a noisy duct, reviewing a duct plan, HVAC coursework |
Frequently Asked Questions
What size duct do I need for 400 CFM?
For a rigid supply trunk at 700 FPM, 400 CFM needs about 10.2 inches, so you'd use a 12-inch round duct. As a rigid supply branch at 600 FPM, it needs about 11.1 inches, which also rounds up to 12 inches.
What size duct for a 6-inch branch?
A 6-inch round branch at the 600 FPM target carries about 118 CFM. At the 900 FPM rigid maximum, it can carry about 177 CFM, but it'll be louder.
Is it better to oversize or undersize ductwork?
Slightly oversized is usually safer than undersized. Undersized ducts raise velocity and static pressure, which adds noise and cuts airflow. Very oversized ducts waste money and space, and they can make it harder to balance airflow between rooms.
How do I convert a round duct to a rectangular one?
Match the cross-sectional area first, then check friction. The calculator gives you the width at your chosen height and shows the equivalent round diameter. If that equivalent diameter is much smaller than the round size you'd need, go a little wider or taller.
Why is flex duct sized differently?
Flex duct has a ridged inner liner that creates more friction than smooth metal. Manual D sets lower maximum velocities for flex, and installation quality matters a lot. Pull it fairly tight and avoid sharp bends.
Why is my duct whistling?
Whistling usually means air is moving too fast, often through an undersized duct, a partly closed damper or a small register. Enter the duct size and airflow in the calculator. If it shows "High," that's likely the cause.
Does this calculator replace Manual D?
No. It handles the velocity check for single duct sections. A full Manual D design also balances pressure across every run, accounts for fittings and matches the blower's available static pressure.
Conclusion
Good duct sizing starts with two numbers: the airflow you need and the velocity limit for that part of the system. Divide one by the other, convert to a diameter or width, and round up to a standard size. Then check that the actual velocity stays within the Manual D range.
Use the calculator above to size a new run or check one you already have.